Feature&Advantages:

Low price and high reliability

Universal AC input

High efficiency and low operation temperature

Soft-start current can reduce the AC input impact effectively

With short-circuit and overload protection

Compact size,light weight

100% full-load burn-in test

Install with EMI filter,minimum wave

Can replace Meanwell brand

 

Specification:

Model

SC-120-12

SC-120-24

 

 

 

output

DC voltage

CH1:13.8V

CH1:13.4V

CH1:27.6V

CH2:26.5V

Voltage tolerance

±1%

-----

±1%

-----

Rated current

8A

0.5A

4A

0.3A

Current range

0~8A

-----

0~4A

-----

Rated power

117.1W

118.4W

Ripple&noise

120mvp-p

-----

180mvp-p

-----

DCvoltage ADJ.range

CH1:11.3~14.9V

CH1:21.3~29.8V

 

 

input

Voltage range

90~264VAC,127~370VDC

frequency

47~63HZ

AC current

2.8A/115VAC,1.4A/230VAC

efficiency

81%

83%

Inrush current

Cold start current  30A/115VAC,50A/230VAC

Leakage current

< 1mA/240VAC

 

protection

Over load

Rated output power110%~150%  start over load protection

protection mode: AC charging mode:hiccup mode auto-recovery after fault condition is removed

Battery protection

At low voltage

9.5~11V

20~22V

protection mode:cutoff output

Function

UPS introduction

long-term online floating charge to battery,high charging efficiency,battery can saturate to more than 90% ,cauto-stop charging when it's full,prevent over charging. Effectively extend battery life,AC/battery auto switch,no switch time,no need human guard,

cold-start ,when there is no AC input ,can use battery start UPS,Meet the user's emergency needs

 

   

safety

Withstand voltage

I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC

Isolated resistance

I/P-O/P,I/P-FG,O/P-FG:100M ohms/500VDC

Fitstandard

Safety standard

Compliance to UL60950-1

EMC standard

Compliance to EN55022,CLASSB

others

Dimension

159*97*38mm (L*W*H)

Weight/packing

0.56kg/45pcs/26kg/0.041m⊃3;/1.45CUFT